Aluminium Conductor XLPE Insulated Overhead Aerial Bundle Power Cable

Model NO.: ABC
Brand: Jiapu
Trademark: JP
Transport Package: Export Wooden Drum or Wooden Steel Drum
Origin: China
HS Code: 8544492100
Aluminium Conductor XLPE Insulated Overhead ABC Cable

Applications:
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connect to the service entrance cable. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75° C for PE insulated Conductors or 90° C for crosslinked polyethylene (XLPE) insulated conductors.

Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR. One conductor is manufactured with an extruded ridge for phase identification.

Installation:
For service at 600 volts or less (phase to phase) at a maximum conductor temperature of 75 0C for Polyethylene insulation or 90 0C for Cross-Linked (XLPE) insulation

Specifications
Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
B-230 Aluminum Wire, 1350-H19 for electrical purposes
B-231 Aluminum Conductors, concentric-lay-stranded
B-232 Aluminum Conductors, concentric-lay-stranded, coated steel reinforced(ACSR)
B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
B-498 Zinc-coated Steel Core Wire for Aluminum Conductors, steel reinforced(ACSR/AZ)

Triplex Service Drop cable meets or exceeds all aplicable requierements of
ANSI/ICEA S-76-474.

Remarks:
1) Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent
Resistivity per ASTMB-399 for 6201.
2) Conductor temperature of 90° C for XLPE 75° C for PE; Ambient temperatures of
40° C; Emissivity 0.9; 2ft. /sec/wind in sun.

The advantages of our company:

1) Our company is a professional supplier of various kinds of cables for over 10 years.
2) The quality of our products are guaranteed.
3) The price is averagely 10%~20% lower than the other competitors
4) Huge Inventory Allows Us To Ship Your Order Immediately
5) Our employees are all capable and professinal. They can offer you the Prompt Courteous Service.
6) We ship worldwide.

Specification:
(1)Self-supporting
Phase Phase Phase Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE Compact Conductor UV-XLPE Insulation
No.X Normal Cross Section of Cores No.of Al Wires Overall Diameter Normal Thickness Min. Diameter
No. X mm2 - mm mm mm mm mm ohm/km
1 X 10 7 4.05 1.0 0.8 6.05 6.05 3.08
1 X 16 7 4.8 1.2 0.98 7.2 7.20 1.91
1 X 25 7 6 1.2 0.98 8.4 8.40 1.20
1 X 35 7 7.0 1.4 1.16 9.8 9.80 0.868
1 X 50 7 8.3 1.4 1.16 11.1 11.10 0.641
1 X 70 19 9.8 1.4 1.16 12.6 12.60 0.443
1 X 95 19 11.6 1.6 1.34 14.8 14.80 0.320
1 X 120 19 13 1.6 1.34 16.2 16.20 0.253
1 X 150 19 14.6 1.8 1.52 18.2 18.20 0.206
1 X 185 36 16.2 2.0 1.70 20.2 20.20 0.164
1 X 240 36 18.4 2.2 1.88 22.8 22.80 0.125
2 X 10 7 4.05 1.0 0.8 6.05 12.10 3.08
2 X 16 7 4.8 1.2 0.98 7.2 14.40 1.91
2 X 25 7 6 1.2 0.98 8.4 16.80 1.20
2 X 35 7 7.0 1.4 1.16 9.8 19.60 0.868
2 X 50 7 8.3 1.4 1.16 11.1 22.20 0.641
2 X 70 19 9.8 1.4 1.16 12.6 25.20 0.443
2 X 95 19 11.6 1.6 1.34 14.8 29.60 0.320
2 X 120 19 13 1.6 1.34 16.2 32.40 0.253
2 X 150 19 14.6 1.8 1.52 18.2 36.40 0.206
2 X 185 36 16.2 2.0 1.70 20.2 40.40 0.164
2 X 240 36 18.4 2.2 1.88 22.8 45.60 0.125
3 X 10 7 4.05 1.0 0.8 6.05 13.07 3.08
3 X 16 7 4.8 1.2 0.98 7.2 15.55 1.91
3 X 25 7 6 1.2 0.98 8.4 18.14 1.20
3 X 35 7 7.0 1.4 1.16 9.8 21.17 0.868
3 X 50 7 8.3 1.4 1.16 11.1 23.98 0.641
3 X 70 19 9.8 1.4 1.16 12.6 27.22 0.443
3 X 95 19 11.6 1.6 1.34 14.8 31.97 0.320
3 X 120 19 13 1.6 1.34 16.2 34.99 0.253
3 X 150 19 14.6 1.8 1.52 18.2 39.31 0.206
3 X 185 36 16.2 2.0 1.70 20.2 43.63 0.164
3 X 240 36 18.4 2.2 1.88 22.8 49.25 0.125
4 X 10 7 4.05 1.0 0.8 6.05 14.64 3.08
4 X 16 7 4.8 1.2 0.98 7.2 17.42 1.91
4 X 25 7 6 1.2 0.98 8.4 20.33 1.20
4 X 35 7 7.0 1.4 1.16 9.8 23.72 0.868
4 X 50 7 8.3 1.4 1.16 11.1 26.86 0.641
4 X 70 19 9.8 1.4 1.16 12.6 30.49 0.443
4 X 95 19 11.6 1.6 1.34 14.8 35.82 0.320
4 X 120 19 13 1.6 1.34 16.2 39.20 0.253
4 X 150 19 14.6 1.8 1.52 18.2 44.04 0.206
4 X 185 36 16.2 2.0 1.70 20.2 48.88 0.164
4 X 240 36 18.4 2.2 1.88 22.8 55.18 0.125
(2) Phase + Neutral
Phase Neutral Phase Neutral Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE AAAC Compact Conductor UV-XLPE Insulation Conductor
Phase Neutral
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.of Al.Wire Overall Dia. Normal Thickness Min. No./Dia. of Al Alloy Wire
No. X mm2 No. X mm2 - mm    mm Min. No./mm      mm ohm/km ohm/km
1 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 12.30 1.91 2.217
1 X 25 1 X 25 7 6 1.2 0.98 7/2.10 14.70 1.20 1.393
1 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 17.30 0.868 1.007
1 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 20.10 0.641 0.744
1 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 23.10 0.443 0.514
1 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 27.30 0.320 0.371
1 X 120 1 X 120 19 13 1.6 1.34 19/2.80 30.20 0.253 0.294
1 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 33.95 0.206 0.239
1 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 37.70 0.164 0.190
1 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 43.05 0.125 0.145
2 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 14.04 1.91 2.217
2 X 25 1 X 25 7 6 1.2 0.98 7/2.10 16.63 1.20 1.393
2 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 19.51 0.868 1.007
2 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 22.46 0.641 0.744
2 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 25.70 0.443 0.514
2 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 30.31 0.320 0.371
2 X 120 1 X 120 19 13 1.6 1.34 19/2.80 33.41 0.253 0.294
2 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 37.55 0.206 0.239
2 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 41.69 0.164 0.190
2 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 47.41 0.125 0.145
3 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 16.15 1.91 2.217
3 X 25 1 X 25 7 6 1.2 0.98 7/2.10 19.06 1.20 1.393
3 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 22.32 0.868 1.007
3 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 25.59 0.641 0.744
3 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 29.22 0.443 0.514
3 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 34.42 0.320 0.371
3 X 120 1 X 120 19 13 1.6 1.34 19/2.80 37.87 0.253 0.294
3 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 42.56 0.206 0.239
3 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 47.25 0.164 0.190
3 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 53.63 0.125 0.145
(3) Phase + Neutral + Service Connection
Phase Neutral Service Connection Phase Neutral     Service Connection Approx.Overall Diameter of Bundled Cable
AAC+UV-XLPE AAAC+UV-XLPE AAC+UV-XLPE Conductor UV-XLPE Conductor UV-XLPE Compact Conductor UV-XLPE
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No. of Al. Wire Overall Dia. Normal
Thickness
No./Dia. of Al. Wire Normal
Thickness
No. of Al. Wire Overall Dia. Normal
Thickness
No. X mm2 No. X mm2 No. X mm2 - mm mm mm mm No./mm mm mm mm
3 X 16 1 X 50 1 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 1 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 1 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 1 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 1 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 1 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 1 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2
3 X 16 1 X 50 2 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 2 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 2 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 2 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 2 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 2 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 2 X 16 19 13 1.6 7/3.0  